﻿id	summary	reporter	owner	description	type	status	priority	milestone	component	version	resolution	keywords	cc
810	24 Jan 14:50 20 KV main power supply problem	ryaya		A problem in the main power supply was detected. Failure detection on the start sequence caused by the primary limiting resitor stage. A bypass vacuum relay was broken and this caused an overload in the starting sequence for the HV power supply. The vacuum relay was replaced for a new one and the problem was solved.	Transmitters	new	normal	2016_01_3 MST-ISR-EEJ	ISR				