Opened 9 years ago

#191 new Transmitters

08 Apr 07:00 Transmitter Power Measurements

Reported by: vquesada Owned by:
Priority: normal Milestone: 2015_04 MST - ISR -EEJ
Component: ISR Version:
Keywords: Cc:

Description

00:00 TX Power sample (-70 dB coupling)
Tx1 +4.9 dBm
Tx2 +4.5 dBm
Line voltage and power: 4080 VAC, 310 Kw
00:07 HV OFF
00:07 High voltage switch failure in a phase limiting resistor 4160 VAC
03:25 HV ON Txs OK.
03:25 TX Power sample (-70 dB coupling)
Tx1 +4.8 dBm
Tx2 +4.4 dBm
Line voltage and power: 4040 VAC, 300 Kw
04:00 TX Power sample (-70 dB coupling)
Tx1 +4.9 dBm
Tx2 +4.6 dBm
Line voltage and power: 4080 VAC, 310 Kw
05:00 TX Power sample (-70 dB coupling)
Tx1 +4.9 dBm
Tx2 +4.6 dBm
Line voltage and power: 4080 VAC, 310 Kw
06:00 TX Power sample (-70 dB coupling)
Tx1 +4.9 dBm
Tx2 +4.6 dBm
Line voltage and power: 4080 VAC, 310 Kw
07:00 TX Power sample (-70 dB coupling)
Tx1 +4.9 dBm
Tx2 +4.6 dBm
Line voltage and power: 4080 VAC, 310 Kw.

Change History (0)

Note: See TracTickets for help on using tickets.