159	26 Mar 13:23 Stop power transmission	dcordova	dcordova	"Because of a failure in the water pump, we have to stpo thw power transmission.
One of the phases of low pressure water-pump showed  high current, compared with the other phases, so this activated the current protection of this pump, besides generated a signal alarm in the transmitter control program.
The currents that we measured when the pump is turn on are(A): 55,53, 71
Then, we changed the pump for another, the currents that we measured when the pump is turn on are(A): 54,54, 54
The voltages in the pump are 470VAC
"	Break Experiment	assigned	high	2015_03 ISR + Imaging CNOFS Support	ISR				