﻿id	summary	reporter	owner	description	type	status	priority	milestone	component	version	resolution	keywords	cc	parents
1866	27 Nov 00:20 Transmitter Power Measurements	vquesada		"20:00 TX Power sample (-70 dB coupling)
Tx1 +5.2 dBm
Tx2 +2.3 dBm
Tx4 +2.1 dBm
D3  -5.8 dBm
Line voltage and power: 4050 VAC, 300 KW
20:40 HV OFF
1)Se quema cable de una fase de salida 440 Vac del variac de la fuente de filamento Tx2.
2)Problemas en el sensor de flujo del Tx4, no habilita la secuencuencia, se purga y despues ok.
22:35 HV ON, Txs OK
22:45 TX Power sample (-70 dB coupling)
Tx1 +5.4 dBm
Tx2 +2.4 dBm
Tx4 +2.4 dBm
D3  -5.6 dBm
Line voltage and power: 4080 VAC, 300 KW
23:30 TX Power sample (-70 dB coupling)
Tx1 +5.1 dBm
Tx2 +2.4 dBm
Tx4 +2.4 dBm
D3  -5.6 dBm
Line voltage and power: 4080 VAC, 300 KW
"	Transmitters	new	normal	2014_11 ISR + Imaging Nov 24-28	ISR					